Mitsubishi Electric QE81WH4W v3 User's Manual
 
                                 en
                                                    en
                                                Energy Measuring Module Model QE81WH4W
Users Manual Hardware
Before using this module, please read both this manual and Details carefully and pay full attention to safety to handle this module correctly.
Make sure that the end users read this manual and then keep the manual in a safe place for future reference. ABOUT MANUALS
The following manuals are also related to this module. Order each manual as needed, referring to the following list.
Manual name Manual numbermodel code
Energy Measuring Module Users ManualDetails QE81WH4W IB6370419H861
COMPLIANCE WITH THE EMC AND LOW VOLTAGE DIRECTIVES (1) For programmable controller system
To configure a system meeting the requirements of the EMC and Low Voltage Directives when incorporating the Mitsubishi programmable controller (EMC and Low Voltage Directives compliant) into other machinery or equipment, refer to Chapter 9 "EMC AND LOW VOLTAGE DIRECTIVES" of the QCPU User's Manual (Hardware Design, Maintenance and Inspection). The CE mark, indicating compliance with the EMC and Low Voltage Directives, is printed on the rating plate of the programmable controller.
(2) For this module For the compliance of this module with the EMC and Low Voltage Directives, refer to Section 6.1 Wiring.
(1)This Energy Measuring module can measure various types of electric quantity just ONE module. This Energy Measuring module can measure electric energy, reactive energy, current, voltage, power, power factor, and frequency. Both consumption and regeneration of the electric energy can be measured.
(2)Extensive monitoring functions In addition to memorizing the maximum and minimum values, two types of alarm monitoring for upper and lower limit can be performed.
(3)It also can measure the electric energy for a certain period. It can measure the electric energy for the duration of time for which the output device is on. This feature enables to acquire the electric energy needed during device operation or energy per tact.
The following items for this device are included in the package. Check that no items are missing. Energy Measuring module x 1 Users Manual (Hardware) x 1
3.1 Precautions for Operating Environment and Conditions Do not use this product in the places listed below. Failure to follow the instruction may cause malfunctions and a life decrease of product.
Places the Ambient temperature exceeds the range 0 55C. Places the Relative humidity exceeds the range 5 95% or places with dewfall. Altitude exceeds 2000 m. Places exposed to rain or water drop. Dust, corrosive gas, saline and oil smoke exist. Vibration and impact exceed the specifications. Installed excluding the control panel.
3.2 Matters concerning the preparation before use Use the module in the specified usage environment and conditions. The setting of this moduleprimary voltage, primary current necessary before using it. Please refer to "Users Manual (Details)" about each setting method.
3.3 Installation and Wiring Precautions
Danger Shut off the external power supply for the module in all phases before installing or wiring. Failure to do so may cause an electric shock or damage of the module.
Caution
Any person who is involved in the installation and the wiring of this Sequencer should be fully competent to do the work. Use the programmable controller in an environment that meets the general specifications in the Users Manual for the CPU module used. Failure to do so may result in electric shock, fire, malfunction, or damage to or deterioration of the product.
To mount the module, while pressing the module-mounting lever located in the lower part of the module, fully insert the module fixing projection(s) into the hole(s) in the base unit and press the module until it snaps into place. Incorrect mounting may cause malfunction, failure or drop of the module. When using the Sequencer in an environment of frequent vibrations, fix the module with a screw.
Tighten the screw within the specified torque range. Under tightening can cause drop of the screw, short circuit or malfunction. Over tightening can damage the screw and/or module, resulting in drop, short circuit, or malfunction.
Shut off the external power supply for the system in all phases before mounting or removing the module. Failure to do so may result in damage to the product.
Do not directly touch any conductive part of the module. Doing so can cause malfunction or failure of the module. FG terminal must be grounded according to the D-type ground (Type 3) dedicated for sequencer. Failure to do so may result in an electric shock or a malfunction.
When using this product, make sure to use it in combination with current sensor (EMU-CT series or EMU2-CT5-4). Please not to exceed the rating of this product for input of current sensor. For further details, please refer to current sensor manual to maintain the functionality and the accuracy of this product.
The dedicated current sensor (EMU-CT50/CT100/CT250/CT400/CT600) is used only for low voltage circuit. It cannot be used with a high voltage circuit. Also, EMU2-CT5-4W should be used with the secondary side (5 A) of transformer transfixed. If it is connected with a high-voltage circuit by mistake, it may cause a burnout of the device and a fire. It is critically dangerous.
Measurement circuit voltage cannot be input directly into the module. Please enter the output voltage of the voltage transform unit (QE8WH4VT)
The dedicated current sensor has a polarity (directionality). Be careful about it when installing the module. Take care not entering any foreign objects such as ships and wire pieces into the module. It may cause a fire, a failure or a malfunction.
In order to prevent the module from incoming foreign objects such as wire pieces during wiring work, a foreign-object preventive label is placed on the module. While a wiring work is performed, keep the label on the module. Before operating the system, peel off the label for heat release. If the foreign-object preventive label is not peeled and the system is in use, residual heat inside the module may reduce the product life.
The wires to be connected to the module shall be placed in a duct or fixed together by clamping. If the electric wires are not placed in the duct or clamped together, loosen wires or their movement or careless stretch may cause a breakage of the module or wire or a malfunction due to poor contact of electric wires.
Use appropriate size of electric wires. If inappropriate size of electric wire is used, it may cause a fire due to generated heat.
In case using stranded wire, take measures so that the filament should not vary by using a bar terminal or by processing the point twisted. Use the bar terminal appropriated for the size of electric wires. If inappropriate bar terminal is used, a wire breakage or a contact failure may occur, which may cause a device malfunction, a failure, a burnout, or a fire.
After inserting the electric wire or a bar terminal, make sure that no missing insertion is existing. Missing insertion may cause a device malfunction, a fire, or an electric shock.
or the wire. If the wires connected to the module are strongly pulled off, it may cause a malfunction or a breakage to the module
Ensure the wiring to the module properly, checking the rated voltage and current of the product and the terminal pin assignment. If the input voltage exceed the rated voltage or the wiring is improper, it may cause a fire or a breakage. (Tensile load: 22N or less)
Do not exceed the specified voltage when doing an insulation resistance test and a commercial frequency withstand voltage test.
To protect persons who do not have adequate knowledge of electric equipment from electric shocks, any of
the following measures should be taken for the panel.
(a) To lock the panel so that only trained persons having adequate knowledge of electric equipment can open it.
(b) To design the structure so that the power is automatically interrupted upon opening of the panel. The protection class of the panel should be IP2X or higher.
Mitsubishi Programmable Controller
3.4 Precautions for Start-up and Maintenance
Caution
Use the product within the ratings specified in this manual. If it is used outside the ratings, it may cause not only malfunction or failure but also fire or burnout.
Before operating the product, check that active bare wire, etc. does not exist around the product. If any bare wire is found, stop the operation immediately, and take an appropriate action such as isolation protection.
Do not disassemble or modify the module. It may cause failure, malfunction, injury or fire. Attaching and detaching the module must be performed after the power source is shut off for all outside
phases. If all phases are not shut off, it may cause electric shock, failure or malfunction of the module. Do not touch powered wires. It may cause malfunction. Tighten mounting screws and cleaning module must be performed after the power source is shut off for all outside phases. If all phases are not shut off, it may cause electric shock,failure or malfunction of the module.
Use a soft dry cloth to clean off dirt of the module surface. Do not let a chemical cloth remain on the surface for an extended period of time nor wipe the surface
with thinner or benzene. Check for the following items to use this module properly for long time. 
or heat. 
3.5 Disposal Precautions When disposing of this module, treat it as industrial waste.
4.1 Names and functions of parts of QE81WH4W are provided below.
(1)LED Operation status of this module is displayed. (Refer to 7-4.)
(3) Current input terminals Connect the secondary output of the dedicated current sensor which has been connected to the measuring circuit.
(4) Voltage input terminals Connect the output wire of the Voltage transform unit.
(5) Push button Use this button to insert a cable to the terminal or to remove them.
(6) Check hole Use this for continuity check to the terminal. Use it with a tester contact.
(7) Strip gauge A gauge that is used for checking the length of stripped wire which is connecting to voltage input terminals.
(2) Strip gauge A gauge that is used for checking the length of stripped wire which is connecting to current input terminals.
Supplementary ---------------------------------------------------------------------------------------------------------------------------------------------- Check the stripping length using the strip gauge of QE81WH4W main module.
4.2 Names and functions of LEDs The following describes names and functions of LEDs.
Name Color Role Indicator condition
RUN LED Green Displays the operation status of this module. ON: Normal operation OFF: 5V power discontinuity, watch dog timer error
ERR. LED Red Displays errors and conditions of this module.
ON: Error occurring (except out-of-range error) *1 Flashing: Out-of-range error *1 OFF: Normal operation
ALM1 LED Red Displays alarm 1 occurrence status.
Flashing: Alarm 1 occurring ON: Alarm 1 occurring Not occurring
(In the case of alarm 1 reset method = self-retention)
OFF: Alarm 1 not occurring
ALM2 LED Red Displays alarm 2 occurrence status.
Flashing: Alarm 2 occurring ON: Alarm 2 occurring Not occurring
(In the case of alarm 2 reset method = self-retention)
OFF: Alarm 2 not occurring
MEA. LED Green Displays the status of measurement of this module.
Flashing: Measurement existing(consumption) ON: Measurement existing(regeneration) OFF: Measurement not existing (no measurement)
1 LED Green Displays the status of measurement (regeneration)at side 1 of this module.
ON: Measurement at side 1 existing (regeneration) OFF: Other than the above
2 LED Green Displays the status of measurement (regeneration) at side 2 of this module.
ON: Measurement at side 2 existing (regeneration) OFF: Other than the above
3 LED Green Displays the status of measurement (regeneration) at side 3 of this module.
ON: Measurement at side 3 existing (regeneration) OFF: Other than the above
1For details, check with the list of error codes. (Refer to section 9.1)
5.1 How to attach to the base unit
Attach to the base unit of MELSEC-Q series. When attaching the module, make sure to insert the protruding portions for fixing the module into the holes on the base unit. In doing so, insert it securely so that the protruding portion of the module does not come off of the holes. Do not force to attach the module; otherwise the module may break.
When installing the module at a vibrating area with strong impact, tighten the module to the base unit using screws. Fixing-Module screw (arranged by user): M3 x 12mm Tightening torque of the fixing-module screws:0.36 0.48 Nm
Terminal symbol Name of terminal
1k
1l
1-phase current input terminal (power source side) 1-phase current input terminal (load side)
2k
2l
2-phase current input terminal (power source side) 2-phase current input terminal (load side)
3k
3l
3-phase current input terminal (power source side) 3-phase current input terminal (load side)
PA PB PC PD
Voltage input terminals (Connect the output wire of the voltage transform unit)
SLD shield terminal
Names of signals of terminal block
Insert it securely so that the protruding portion for fixing the module*1 does not come off of the module-fixing hole.
Push the unit toward the arrow direction, as the module-fixing hole being a fulcrum point, until you hear a click sound to firmly attach it to the based module.
Check that the module is firmly inserted to the base unit.
Complete
Base unit
Module
Unit connector Base unit
Protrusion for fixing the module (*1)
Lever for attaching the module
6.1 Wiring Follow the wiring diagram for external connection of QE81WH4W. Current sensor (EMU-CT50/CT100/CT250/CT400/CT600, EMU2-CT5-4W) is necessary for the connection of the current circuit. Voltage transform unit (QE8WH4VT) is necessary for the connection of the voltage circuit.In addition,up to five QE81WH4W modules can be connected to one voltage transform unit. Please refer to the Users Manual (Details) of this module,and the installation method and the detailed specifications of the current sensor and the voltage transform unit.
Make sure that before connecting the cable, the directionof the current sensor is correct for attachment. K to L is the correct direction. K: power source side, L: load side.
The available range of the voltage transform unit is from 55/95VAC to 227/480VAC. When this product is used in a circuit more than 227/480VAC,voltage transformer is required. The available phase voltage of the transformer is up to 6600V. Connect the secondaryside of the transformer to the terminal (P1, P2, P3, P0) of the Voltage transform unit.Make sure that terminal symbols are correct. This product cannot connect with the secondary side of the transformer directly.
6.2 How to connect wires Use appropriate electric wires and tighten a screw by appropriate torque as described right. Insert a wire to the terminal all the way until it touches the end. Voltage input terminals Stripping length of the used wire in use has to be 5 to 6mm. Check the stripping lengthusing the strip gauge of
QE81WH4W module. When stranded wire is used, twist the tip. Current input terminals When attaching and detaching cables to/from the terminal, use the push button. Check that the wire is securely inserted.
Stripping length of the used wire in use has to be 10 to 11mm. Check the stripping length using the strip gauge of QE81WH4W module. When stranded wire is used, a bar terminal or the tip-twisting are required to avoidwire scatting. Recommended bar terminals for current input terminals: TGV TC1.25-11T (NICHIFU TERMINAL INDUSTRIES CO.,LTD)
Voltage input terminals Current input terminals
Single wire AWG24-16
AWG26-16
Stranded wire AWG26-14
Tightening torque [Nm] 0.25 -
UL/c-UL listed corresponds, use the wires according to the following conditions. Voltage input terminals: AWG24-14 (Single wire / Stranded wire) Current input terminals: AWG24-18 (Single wire) , AWG26-18 (Stranded wire) 60/75 copper conductor only.
Terminals de tension d'entre Terminals de courant d'entre
Cble simple AWG24-16
AWG26-16
Cble brin AWG26-14
Couple de serrage [Nm] 0.25 -
Pour tre conforme UL/c-UL standard, utilisez le fil lectrique selon les conditions suivantes. Terminals de tension d'entre: AWG24-14 (Cble simple / Cble brin) Terminals de courant d'entre: AWG24-18 (Cble simple), AWG26-18 (Cble brin) Seulement le conduit en cuivre 60C/75C.
Caution
Input signal wire shall not be bound together with or placed close to the main circuit and power line. Keep 300 mm or longer distance between them. (Except for the terminal input section) It may cause malfunction due to noise
The input wiring of the measurement circuit uses separate cables which is different from other signal cables, and do not be affected by serge and the instruction of the interchange side.
In actual use, connect the SLD terminal to a shield.
EMU-CT*** model split current sensor 50/100/250/400/600
Three-phase 4-wire(with the voltage transform unit / Separated type current transformer)
Load side
Power source side
QE8WH4VT Voltage transform unit
Three-phase 4-wire(with the voltage transform unit / voltage transformer / current transformer)
Power source side
Load side
Voltage transformer
Current transformer ***/5A
5A current sensor cable EMU2-CB-Q5A-4W
5A current sensor EMU2-CT5-4W
Note: Unit of number is mm. The charge-free warranty period for the product shall be 1 year from the date of your purchase or the date the product is delivered to your specified delivery location However, the maximum limit of the charge-free warranty period shall be set to 18 months from the time of manufacture by defining the longest distribution period of the product as 6 months after the product is shipped from our manufacturing factory. Also, the charge-free warranty period for the replacement product shall not be extended exceeding the charge-free warranty period for the original product.
Our company shall not be liable to compensate for any loss arising from events not attributable to our company, opportunity loss and lost earning of the customer due to failure of the product, and loss, secondary loss, accident compensation, damage to other products besides our products and other operations caused by a special reason regardless of our companys predictability in both within and beyond the charge-free warranty period.
Caution If an abnormal sound, bad-smelling smoke, fever break out from this module, I switch it off promptly, and dont use it.
Item Specifications Model QE81WH4W Phase-wire system three-phase 4-wire
Rating
Voltage circuit
63.5/110 277/480V AC Selected from: 63.5/110V100/173V105/182V
110/190V 115/199V 120/208V 127/220V
200/346V 220/380V 230/400V 240/415V
242/420V 250/430V 254/440V 265/460V 277/480V Each value refers to the primary voltage of voltage transform unit.
Current circuit
50 A, 100 A, 250 A, 400 A, 600 A AC (The dedicated split type current sensor is used. Each value refers to the current at the primary side of the current sensor.) 5A AC (The dedicated split type current sensor is used. 5 A current sensor is used together with the current transformer (CT), and the primary-side current is configurable up to 6000 A.)
Frequency 50Hz-60Hz
Allowable tolerance of module (excluding the current sensor)
Current : 1.0% (100% of the rating) Voltage : 1.0% (100% of the rating) Electric power : 1.0% (100% of the rating) Reactive power: 1.0% (100% of the rating) Apparent power: 1.0% (100% of the rating) Frequency : 1.0% (45 65 Hz range of the rating) Power factor : 3.0% (against the electric angle 90) Electric energy : 2.0%
(5 100% range of the rating, power factor = 1) Reactive energy : 2.5%
(10 100% range of the rating, power factor = 0) Measurable circuit count 1 circuit Operating temperature 0 55C (Average daily temperature 35C or below) Operating humidity 5 95% RH (No condensation) Storage temperature -25 +75C Operating altitude 2000 m or below
Commercial frequency withstand voltage
Between voltage/current input terminals - SLD terminal: 2210 V AC5 sec
Between voltage/current input terminals - sequencer power source and GND terminals:
2210 V AC5 sec
Standard EMC LVD
:EN61131-2:2007, EN61326-1:2006 :EN61131-2:2007, EN61010-1:2001
Installation area Inside a control panel KCC-REI-MEK-19H011
Appllicant MITSUBISHI ELECTRIC AUTOMATION KOREA CO.Ltd
Equipment Name Energy Measuring Module
Model QE81WH4W
Made In JAPAN
Manufacturer
MITSUBISHI ELECTRIC CORPORATION FUKUYAMA WORKS
A ( )
,
.
(A)
1. Features
2. Checking packaged contents
3. Safety Precautions
4. Name and function of each part
5. Attaching and removing the module
module(*2) Hook for fixing the
Hole for fixing the module
P1
P2
P3
P0
FG
PD
SLD
PB
PA
PC
1k
1l
2k
2l
3k
3l
PA
PB
PC
PD
SLD
K
L K
L K
L
1 2 3 0
QE81WH4W
3
2
1
1
2
P1
P2
P3
P0
FG
PD
SLD
PB
PA
PC
1k
1l
2k
2l
3k
3l
PA
PB
PC
PD
SLD
1 2 3 0
QE81WH4W
3
2
1
1
2
7. Dimensions 8. Specifications 9. Warranty
6. How to wire
10. Customer Service
QE81WH4W
DP
SLD
PC
PB
PA
1k
1l
2k
3k
3l
2l
10 S
T R
IP G
A U
G E
S T
R IP
G A
U G
E 5
98
90.5 27.4
4
QE81WH4W
3
2
1
1
2
QE81WH4W
3
2
1
1
2
QE81WH4W
DP
SLD
P