Mitsubishi Electric FX2N 2DA User's Guide
![Mitsubishi Electric FX2N 2DA manual cover](/images/8975b13a1cf80f4a6fb777d9/thumbs/thumb175x175.webp)
To connect the FX2N-2DA to your PLC system, ensure that the module is mounted on a DIN rail adjacent to the base unit. Connect the extension cable from the base unit to the FX2N-2DA and ensure that the power supply is correctly wired to the module.
To configure the analog output channels, first designate the channel settings in your PLC program. Use the appropriate FROM/TO instructions to set the output values. Refer to the programming manual for specific register settings.
Check all wiring connections for secure contact. Verify the configuration settings in the PLC program and ensure that the correct registers are being used. Additionally, measure the output using a multimeter to confirm the output levels.
Regularly inspect the module for dust and debris and clean with a soft brush or compressed air. Ensure that all connections are tight and free from corrosion. Periodically check the output levels to ensure accuracy.
No, the FX2N-2DA cannot output both voltage and current simultaneously on the same channel. Each channel can be configured for either voltage or current, but not both at the same time.
Mitsubishi FX2N-2DA modules do not typically require firmware updates as they are designed for specific hardware functionality. Ensure you have the latest PLC programming software for best compatibility.
To expand beyond two analog outputs, additional FX2N-2DA modules can be connected to the PLC system. Each module provides two extra analog outputs. Ensure your PLC system can handle the additional modules.
When wiring the FX2N-2DA, ensure that power is off to prevent electrical shock. Use shielded cables to minimize electrical noise, and follow the wiring diagrams provided in the manual to prevent incorrect connections.
The FX2N-2DA does not have a factory reset function. Configuration settings are controlled through the PLC software, and you can reprogram the relevant registers to the default state as needed.
The FX2N-2DA can handle a maximum load of 600 ohms for current output (4-20mA) and a minimum load of 2k ohms for voltage output (0-10V). Ensure your connected devices fall within these parameters.