Viessmann Vitogas 100 GS1 Series Operating Instructions
![Viessmann Vitogas 100 GS1 Series Boiler manual cover](/images/CIMgjoSNNhtwGQPpCMyTcmeT/thumbs/thumb175x175.webp)
![English English](/static/img/blank.webp)
VITOGAS 100
Operating Instructions and Users Information Manual
Vitogas 100 GS10 Series Natural gas-/propane-fired, two-stage atmospheric cast iron boiler
Heating input 300 to 380 MBH 88 to 111 kW
If the information in this manual is not followed exactly, a fire or explosion may result causing property damage, personal injury or loss of life.
WARNING
Improper installation, adjustment, and/or operation could cause carbon monoxide poisoning resulting in injury or loss of life.
This product must be installed and serviced by a professional service technician who is experienced and qualified in hot water boiler installation and gas combustion.
WARNING
Do not store or use gasoline or other flammable liquids in the vicinity of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS Do not try to light any appliances. Do not touch any electrical switches, do not use any phone in your building. Immediately call your gas supplier from a neighbors phone. Follow the gas suppliers instructions. If you cannot reach your gas supplier, call the fire department.
Installation and service must be performed by a qualified installer, service agency or the gas supplier.
Read and save these instructions for future reference.
IMPORTANT
5167 469 v1.1 12/2003
Pl ea se fil e in Se rv ic e B in de r
Safety, Installation and Warranty Requirements
2
Safety, Installation and Warranty Requirements
Please ensure that these instructions are read and understood before commencing installation. Failure to comply with the instructions listed below and details printed in this manual can cause product/property damage, severe personal injury, and/or loss of life. Ensure all requirements below are understood and fulfilled (including detailed information found in manual subsections).
H Licensed professional heating contractor The installation, adjustment, service, and maintenance of this equipment must be performed by a licensed professional heating contractor.
" Please see section entitled Important Regulatory and Installation Requirements in the Installation Instructions.
H Product documentation Read all applicable documentation before commencing installation. Store documentation near boiler in a readily accessible location for reference in the future by service personnel.
" For a listing of applicable literature, please see section entitled Important Regulatory and Installation Requirements in the Installation Instructions.
HAdvice to owner Once the installation work is complete, the heating contractor must familiarize the system operator/ultimate owner with all equipment, as well as safety precautions/requirements, shut-down procedure, and the need for professional service annually before the heating season begins.
HContaminated air Air contaminated by chemicals can cause by-products in the combustion process which are poisonous to inhabitants and destructive to Viessmann equipment.
" For a listing of chemicals which cannot be stored in or near the boiler room, please see section entitled Combustion Air Supply in the Installation Instructions.
HCarbon monoxide Improper installation, adjustment, service and/or maintenance can cause flue products to flow into living space. Flue products contain poisonous carbon monoxide gas.
" For information pertaining to the proper installation, adjustment, service and maintenance of this equipment to avoid formation of carbon monoxide, please see sections entitled Combustion Air Supply and Venting Connection in the Installation Instructions.
H Fresh air This equipment requires fresh air for safe operation and must be installed ensuring provisions for adequate combustion and ventilation air exist.
" For information pertaining to the fresh air requirements of this product, please see section entitled Combustion Air Supply in the Installation Instructions.
H Equipment venting Never operate boiler without an installed venting system. An improper venting system can cause carbon monoxide poisoning.
" For information pertaining to venting and chimney requirements, please see section entitled Venting Connection in the Installation Instructions. All products of combustion must be safely vented to the outdoors.
HWarranty Information contained in this and related product documentation must be read and followed. Failure to do so renders warranty null and void.
5 1 6 7 4 6 9 v1
.1 Installers must follow local regulations with respect to installation of carbon monoxide detectors. Follow manufacturers maintenance schedule of boiler.
WARNING
Safety
3
About these Instructions Take note of all symbols and notations intended to draw attention to potential hazards or important product information. These include WARNING, CAUTION, and IMPORTANT. See below.
Warnings draw your attention to the presence of potential hazards or important product information.
Cautions draw your attention to the presence of potential hazards or important product information.
Helpful hints for installation, operation or maintenance which pertain to the product.
This symbol indicates that additional, pertinent information is to be found in column three.
This symbol indicates that other instructions must be referenced.
Safety
H Operation
Before operating the boiler, make sure you fully understand its method of operation. Your heating contractor should always perform the initial start-up and explain the system. Any warranty is null and void if these instructions are not followed.
HWorking on the equipment
All personnel working on the equipment or the heating system must have the proper qualifications and hold all necessary licenses.
Ensure main power to equipment, heating system, and all external controls has been deactivated. Close main gas supply valve. Take precautions in all instances to avoid accidental activation of power during service work.
HMaintenance and cleaning
Regular inspection and service by a qualified heating contractor is critical to the performance of the Viessmann Vitogas 100, GS10. Neglected maintenance impacts on warranty; regular cleaning and maintenance ensures clean, environmentally friendly and efficient operation. We recommend a maintenance contract with a qualified heating contractor.
H Flue gas smell
- Deactivate heating equipment. - Open windows and doors. - Inform your heating contractor.
H Dangerous conditions
- Deactivate main power immediately. - Close gas supply valve.
H Technical information
Literature applicable to all aspects of the Vitogas 100: - Technical Data Manual - Installation Instructions - Start-up/Service Instructions - Operating Instructions and Users Information Manual
Additional applicable literature: - Vitotronic controls manuals - Accessory manuals
5 1 6 7 4 6 9 v1
.1 5 1 6 7 4 6 9 v1
.1
Indicates an imminently hazardous situation which, if not avoided, could result in death, serious injury or substantial product/property damage.
WARNING
Indicates an imminently hazardous situation which, if not avoided, may result in minor injury or product/property damage.
CAUTION
IMPORTANT
Incomplete combustion and poisonous gases result if the fresh air intakes in the mechanical room are closed. Never close these openings.
CAUTION
Safety
4
Safety (continued)
H For safe operation
We recommend that you frequently: - Check for debris which could obstruct the flow of flue gases. The vent or chimney must not be blocked. A blocked or partially blocked vent or chimney can cause flue gases to leak into the structure. Flue gases leaking into the house can cause injury or death. Blocked or partially blocked chimneys must have the blockage removed by a qualified heating contractor.
- Check pressure gage for correct system (water) pressure. Check for water on the floor from the discharge pipe of the pressure relief valve or any other pipe, pipe joint, valve or air vent.
- Check for moisture, water, or appearance of rust on the flue gas pipes, their joints as well as vent dampers, or side wall vent terminals (if so equipped).
- Ensure that nothing is obstructing the flow of combustion and ventilation air and no chemicals, garbage, gasoline, combustible materials, flammable vapors and liquids are stored (not even temporarily) in the vicinity of the boiler.
- Do not allow unsupervised children near the boiler.
Service/inspection of the boiler and the system is recommended once a year. Maintenance, service and cleaning are specified in the Installation Instructions.
Before the heating season begins, the boiler with its burners should be serviced by a qualified heating contractor. Service contracts may be established through gas suppliers or other licensed contractors in your area.
This product comes with several safety instruction labels attached. Do not remove! Contact Viessmann immediately if replacement labels are required.
Do not use this boiler if any part has been under water. Immediately call a qualified heating contractor to inspect the boiler and to replace any part of the control system and any gas control which has been under water.
Do not store chemicals containing chlorine or other corrosive materials near the boiler, such as bleach, cleaning solvents, detergents, acids, hair spray, spray cans, paint thinners, paint, or water softener salt.
5 1 6 7 4 6 9 v1
.1
There are no user serviceable parts on the boiler, burners or control. Failure to heed this warning can cause property damage, severe personal injury, or loss of life.
WARNING
Improper installation, adjustment, service, or maintenance can cause flue products to flow into living space. Flue products contain poisonous carbon monoxide gas which can cause nausea or asphyxiation resulting in severe personal injury or loss of life.
WARNING
Should overheating occur or the gas supply fail to shut off, do not disconnect the electrical supply to the pump. Instead, shut off the gas supply at a location external to the appliance.
CAUTION
The operator/ultimate owner is required to have the heating boiler, burners, and controls checked, as a minimum once per year, by the original installer or by a competent heating contractor familiar with the equipment. Defects must be corrected immediately.
WARNING
IMPORTANT
Operating Instructions
5
Vitogas 100, GS10
Pressure gage
Fuel
This boiler is factory calibrated for use only with the fuel stated on the boiler rating plate.
Boiler is factory supplied for use with one fuel only (natural gas or propane).
Safety switches
Blocked vent safety switch
The manual reset blocked vent safety switch is located at the back of the boiler in the draft hood. In the event of complete vent blockage by snow, ice, debris, animals nests or other material, the spill switch heats up and interrupts 24V to the gas control, thereby shutting down the burner. Do not attempt to reset the switch - call a qualified heating contractor. If the switch activates, the vent system must be checked inside and out. The blockage must be removed by the heating contractor before the boiler is put back into operation. Do not operate the boiler without the blocked vent safety switch being fully operational.
Do not attempt to operate the boiler without the blocked vent safety switch being fully operational. Advise the system operator/ultimate owner to contact a qualified heating contractor for service immediately should the switch activate.
5 1 6 7 4 6 9 v1
.1
System power switch I = Power on O = Power off
Front view
VITOGAS 100
VIEMANN
Rear view
For burner status indication reference applicable Vitotronic control manual.
Do not use propane gas on a boiler equipped for use with natural gas. Do not use natural gas on a boiler equipped for use with propane gas.
WARNING
IMPORTANT
Do not bypass this safety device.
WARNING
Operating Instructions
6
Start-up
Initial start-up
The heating contractor must perform the initial start-up and explain the operation of the system. Refer to Lighting and Operating Instructions on the following page.
The operation of the boiler control must also be explained to the system operator/ultimate owner by the heating contractor. Refer to literature packaged with boiler control.
Necessary preparations prior to initial start-up (as well as for successive start-ups)
1.Check for water on the floor from the discharge pipe of the pressure relief valve or any other pipe, pipe joint, valve or air vent.
If pressure relief valve is discharging, contact contractor to locate source of problem and take corrective measures. Never cap or plug end of pressure relief valve discharge pipe.
Ensure correct system (water) pressure. See pressure gage. If the system pressure is below 10 psig, please call your heating contractor.
2.Ensure fresh combustion air supply vents to boiler room are open and unobstructed.
Nothing must obstruct the flow of combustion and ventilation air.
3.Open main gas supply valve.
4.Activate the system. Ensure power supply is activated and then activate system power switch .
Your heating system is now ready for operation.
Start-up
Refer to Lighting and Operating Instructions on following page. The boiler control regulates operation of the heating system automatically in conjunction with the indoor/outdoor control and any programmed settings (if applicable). Changes to the settings or programming can be made according to separate instructions provided with the boiler control.
For optimum operation
H Keep the boiler and the boiler room clean and free of dust and dirt.
H Ensure proper system pressure by occasionally checking pressure gage.
H Allow a qualified heating contractor to regularly service and maintain your heating system.
Neglected maintenance impacts on product warranty; regular cleaning and maintenance ensures clean, environmentally friendly and efficient operation.
Viessmann recommends a maintenance contract with a qualified heating contractor.
If you require assistance finding a qualified heating contractor, contact Viessmann.
Shut-down
Brief shut-downs
Vitotronic controls
Set system power switch to 0 and ensure main power supply to boiler and control remains activated.
Vitotronic boiler control manuals
Extended shut-downs
1.Close main gas supply valve.
2.Deactivate system power switch.
3.Deactivate main power supply to boiler and control.
We recommend that you contact your heating contractor prior to and after an extended shut-down period. In this manner, the appropriate precautions, i.e. system freeze-up protection or heat exchanger maintenance, can be taken.
5 1 6 7 4 6 9 v1
.1
Under these measures, the heating system remains electrically activated.
CAUTION
Operating Instructions
7
Lighting and Operating Instructions
5 1 6 7 4 6 9 v1
.1
Additional Information
Viessmann Manufacturing Company Inc. 750 McMurray Road Waterloo, Ontario N2V 2G5 Canada Tel. (519) 885-6300 Fax (519) 885-0887 www.viessmann.ca [email protected]
Viessmann Manufacturing Company (U.S.) Inc. 45 Access Road Warwick, Rhode Island 02886 USA Tel. (401) 732-0667 Fax (401) 732-0590 www.viessmann-us.com [email protected]
8
Troubleshooting Guide
Failure Cause Correction
Heating system does not activate System power switch on the boiler control has not been activated.
Activate
Main power supply to boiler and control has not been activated.
Activate
Breaker or fuse in building electrical panel has blown.
Contact heating contractor.
Safety temperature high limit has deactivated.
Contact heating contractor.
Vent damper motor does not open (if applicable).
Contact heating contractor.
Burner does not activate, or does so Fuel supply inadequate Open main gas supply valve. sporadically Boiler control or boiler system control is
improperly set. Ensure proper setting of switching times and program selection switch.
Fault indication on boiler control (if applicable)
Contact heating contractor.
Burner does not activate Ignition system fault Turn off system power switch and wait 5 minutes. Turn on system power switch Do not repeat more than twice. . If unsuccessful, contact heating contractor.
Heating circuit cold Priority to (indirect-fired) DHW production Wait until DHW tank has completed its heating cycle.
Room temperature is too cold or too hot during different periods of the year
Heating curves not properly set Make appropriate adjustments (see Operating Instructions of Vitotronic control).
Please notify your heating contractor in the event of additional fault occurrences.